TempTracker mod+ & TempTracker mod+ Extension Installation Manual 23
MAINTENANCE
Button: MENU/<Maintenance>
The Maintenance menu gives access to sensor and outputs trimming and Soft-Off. In
addition, you'll have access to view the Startup conguration settings.
ALERT
To be able to change the TempTracker mod+ settings the Program/Run Switch
must be set to Program. The switch is located under the Enclosure Wiring Cover
for security. The Enclosure Wiring Cover can be securely closed using a lock.
----------- SETTINGS ------------
Season Winter
Set Point 70 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
---------------- GAIN --------------
+0
F
[ ]
BACK SELECT
---------- SETTINGS 1 ----------
Gain +0
Lead Rotation Last-On
Purge Delay 1.0min
Lag Delay 0min
<More Settings>
BACK SELECT
---------- SETTINGS 2 ----------
Standby Time 7min
System Run-On 10min
Setback 10 F
Last Stage Hold 5 F
Set Time 12:05Pm
<Day/Night Schedules>
BACK SELECT
--- DAY/NIGHT SCHEDULES ---
Set Time **:**
Day Schedule **:**
Night Schedule **:**
BACK SAVE
---- MANUAL LEAD STAGE ----
A
B
C
D
E
BACK SAVE
--- AUTO ROTATE PERIOD ---
24
hrs
[ ]
BACK SAVE
--------- PURGE DELAY ---------
1.0
min
[ ]
BACK SAVE
----------- LAG DELAY -----------
0
min
[ ]
SYSTEM SETTINGS1
SYSTEM SETTINGS2
BACK SAVE
-------- STANDBY DELAY --------
7
min
[ ]
BACK SAVE
-------- SYSTEM RUN-ON --------
10
min
[ ]
BACK SAVE
-------------- SETBACK -----------
10
F
[ ]
BACK SAVE
------ LAST STAGE HOLD ------
5
F
[ ]
BACK SAVE
----- SET PRESENT TIME -----
11:**Pm
SETBACK INPUT
Shutdown
/TStat
BACK SELECT
---------- MAINTENANCE ---------
System Trim +0 F
Outdoor Trim +0 F
Soft-Off Delay 10sec
<Output Trim>
<Configuration>
MAINTENANCE
BACK SAVE
--- SYSTEM SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
-- OUTDOOR SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
------- SOFT-OFF DELAY --------
10
sec
[ ]
BACK SELECT
-------- STAGE A TRIM --------
Output Trim +0.0
<Prev Stage>
<Next Stage>
BACK SAVE
-------------- STAGE A -----------
OUTPUT TRIM
+0.0
[ ]
BACK EXIT
------ CONFIGURATION 2 ------
A=4-20ma B=0-10v
C=0-5v D=2-10v
BACK NEXT
------ CONFIGURATION 1 ------
v1.00c
Reset F
Parallel
Day/Night Schedules
All Off
BACK SAVE
-------- LEAD ROTATION -------
Manual
Time
Last-On
--------
SYSTEM
A
B
C
D
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7
8
9
10
11
12
13
15
14
17
16
18
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
+
mA
22
-
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
CAUTION
: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
SYSTEM & OUTDOOR SENSOR TRIM
Adjustable-5°Fto+5°F Default:0°F
Button: MENU/<Maintenance>/System Trim
Button: MENU/<Maintenance>/Outdoor Trim
• The Raypak thermistor type sensors are very accurate, and normally require no calibration.
Sometimes it may be desirable to make small adjustments to the displayed value for either
the Outdoor temperature (OD) or the System temperature (SYS). The Trim setting can
adjust the displayed value by ± 5°F.
• Do not use the Trim setting to make the Outdoor temperature sensor match that reported on
the radio or TV. Outdoor temperature can vary widely over a broadcast range. Only trim
the outdoor sensor based on an accurate thermometer reading taken where the sensor is
located.
----------- SETTINGS ------------
Season Winter
Set Point 70 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
---------------- GAIN --------------
+0
F
[ ]
BACK SELECT
---------- SETTINGS 1 ----------
Gain +0
Lead Rotation Last-On
Purge Delay 1.0min
Lag Delay 0min
<More Settings>
BACK SELECT
---------- SETTINGS 2 ----------
Standby Time 7min
System Run-On 10min
Setback 10 F
Last Stage Hold 5 F
Set Time 12:05Pm
<Day/Night Schedules>
BACK SELECT
--- DAY/NIGHT SCHEDULES ---
Set Time **:**
Day Schedule **:**
Night Schedule **:**
BACK SAVE
---- MANUAL LEAD STAGE ----
A
B
C
D
E
BACK SAVE
--- AUTO ROTATE PERIOD ---
24
hrs
[ ]
BACK SAVE
--------- PURGE DELAY ---------
1.0
min
[ ]
BACK SAVE
----------- LAG DELAY -----------
0
min
[ ]
SYSTEM SETTINGS1
SYSTEM SETTINGS2
BACK SAVE
-------- STANDBY DELAY --------
7
min
[ ]
BACK SAVE
-------- SYSTEM RUN-ON --------
10
min
[ ]
BACK SAVE
-------------- SETBACK -----------
10
F
[ ]
BACK SAVE
------ LAST STAGE HOLD ------
5
F
[ ]
BACK SAVE
----- SET PRESENT TIME -----
11:**Pm
SETBACK INPUT
Shutdown
/TStat
BACK SELECT
---------- MAINTENANCE ---------
System Trim +0 F
Outdoor Trim +0 F
Soft-Off Delay 10sec
<Output Trim>
<Configuration>
MAINTENANCE
BACK SAVE
--- SYSTEM SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
-- OUTDOOR SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
------- SOFT-OFF DELAY --------
10
sec
[ ]
BACK SELECT
-------- STAGE A TRIM --------
Output Trim +0.0
<Prev Stage>
<Next Stage>
BACK SAVE
-------------- STAGE A -----------
OUTPUT TRIM
+0.0
[ ]
BACK EXIT
------ CONFIGURATION 2 ------
A=4-20ma B=0-10v
C=0-5v D=2-10v
BACK NEXT
------ CONFIGURATION 1 ------
v1.00c
Reset F
Parallel
Day/Night Schedules
All Off
BACK SAVE
-------- LEAD ROTATION -------
Manual
Time
Last-On
----------- SETTINGS ------------
Season Winter
Set Point 70 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
---------------- GAIN --------------
+0
F
[ ]
BACK SELECT
---------- SETTINGS 1 ----------
Gain +0
Lead Rotation Last-On
Purge Delay 1.0min
Lag Delay 0min
<More Settings>
BACK SELECT
---------- SETTINGS 2 ----------
Standby Time 7min
System Run-On 10min
Setback 10 F
Last Stage Hold 5 F
Set Time 12:05Pm
<Day/Night Schedules>
BACK SELECT
--- DAY/NIGHT SCHEDULES ---
Set Time **:**
Day Schedule **:**
Night Schedule **:**
BACK SAVE
---- MANUAL LEAD STAGE ----
A
B
C
D
E
BACK SAVE
--- AUTO ROTATE PERIOD ---
24
hrs
[ ]
BACK SAVE
--------- PURGE DELAY ---------
1.0
min
[ ]
BACK SAVE
----------- LAG DELAY -----------
0
min
[ ]
SYSTEM SETTINGS1
SYSTEM SETTINGS2
BACK SAVE
-------- STANDBY DELAY --------
7
min
[ ]
BACK SAVE
-------- SYSTEM RUN-ON --------
10
min
[ ]
BACK SAVE
-------------- SETBACK -----------
10
F
[ ]
BACK SAVE
------ LAST STAGE HOLD ------
5
F
[ ]
BACK SAVE
----- SET PRESENT TIME -----
11:**Pm
SETBACK INPUT
Shutdown
/TStat
BACK SELECT
---------- MAINTENANCE ---------
System Trim +0 F
Outdoor Trim +0 F
Soft-Off Delay 10sec
<Output Trim>
<Configuration>
MAINTENANCE
BACK SAVE
--- SYSTEM SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
-- OUTDOOR SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
------- SOFT-OFF DELAY --------
10
sec
[ ]
BACK SELECT
-------- STAGE A TRIM --------
Output Trim +0.0
<Prev Stage>
<Next Stage>
BACK SAVE
-------------- STAGE A -----------
OUTPUT TRIM
+0.0
[ ]
BACK EXIT
------ CONFIGURATION 2 ------
A=4-20ma B=0-10v
C=0-5v D=2-10v
BACK NEXT
------ CONFIGURATION 1 ------
v1.00c
Reset F
Parallel
Day/Night Schedules
All Off
BACK SAVE
-------- LEAD ROTATION -------
Manual
Time
Last-On
SOFT-OFF DELAY
Adjustable0secto60sec Default:10sec
Button: MENU/<Maintenance>/Soft-Off Delay
• When a stage is no longer needed, the Soft-Off keeps that stage burner in Low Fire prior to
turning it off.
• The display will show a percent that is equal to the Ignition % for the stage in Soft-Off
delay. That number will blink for the Soft-Off delay period.
• If during the Soft-Off stage delay period the TempTracker mod+ needed that stage to turn
back on, the stage will be released from the Soft-Off delay and resume normal operation.
• On a Shutdown initiation or Tstat termination any stage that was on will go into Soft-Off
delay before fully turning off.
----------- SETTINGS ------------
Season Winter
Set Point 70 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
---------------- GAIN --------------
+0
F
[ ]
BACK SELECT
---------- SETTINGS 1 ----------
Gain +0
Lead Rotation Last-On
Purge Delay 1.0min
Lag Delay 0min
<More Settings>
BACK SELECT
---------- SETTINGS 2 ----------
Standby Time 7min
System Run-On 10min
Setback 10 F
Last Stage Hold 5 F
Set Time 12:05Pm
<Day/Night Schedules>
BACK SELECT
--- DAY/NIGHT SCHEDULES ---
Set Time **:**
Day Schedule **:**
Night Schedule **:**
BACK SAVE
---- MANUAL LEAD STAGE ----
A
B
C
D
E
BACK SAVE
--- AUTO ROTATE PERIOD ---
24
hrs
[ ]
BACK SAVE
--------- PURGE DELAY ---------
1.0
min
[ ]
BACK SAVE
----------- LAG DELAY -----------
0
min
[ ]
SYSTEM SETTINGS1
SYSTEM SETTINGS2
BACK SAVE
-------- STANDBY DELAY --------
7
min
[ ]
BACK SAVE
-------- SYSTEM RUN-ON --------
10
min
[ ]
BACK SAVE
-------------- SETBACK -----------
10
F
[ ]
BACK SAVE
------ LAST STAGE HOLD ------
5
F
[ ]
BACK SAVE
----- SET PRESENT TIME -----
11:**Pm
SETBACK INPUT
Shutdown
/TStat
BACK SELECT
---------- MAINTENANCE ---------
System Trim +0 F
Outdoor Trim +0 F
Soft-Off Delay 10sec
<Output Trim>
<Configuration>
MAINTENANCE
BACK SAVE
--- SYSTEM SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
-- OUTDOOR SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
------- SOFT-OFF DELAY --------
10
sec
[ ]
BACK SELECT
-------- STAGE A TRIM --------
Output Trim +0.0
<Prev Stage>
<Next Stage>
BACK SAVE
-------------- STAGE A -----------
OUTPUT TRIM
+0.0
[ ]
BACK EXIT
------ CONFIGURATION 2 ------
A=4-20ma B=0-10v
C=0-5v D=2-10v
BACK NEXT
------ CONFIGURATION 1 ------
v1.00c
Reset F
Parallel
Day/Night Schedules
All Off
BACK SAVE
-------- LEAD ROTATION -------
Manual
Time
Last-On
ALERT
When using Soft-Off and Last Stage Hold, the last boiler stage will not turn off until both
parameters have elapsed. In this case, Soft-Off will start after the Last Stage Hold.
OUTPUT TRIM
Adjustable-5to+5 Default:0
Button: MENU/<Maintenance>/Output Trim
• Each of the stages controlled by the TempTracker mod+ has a separate Output Trim setting.
• Output Trim acts as an adjustment to a stage output percent to match the burner motor.
• After adjusting the Output Trim, test the operation to make sure the results match your
expectation.
----------- SETTINGS ------------
Season Winter
Set Point 70 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
---------------- GAIN --------------
+0
F
[ ]
BACK SELECT
---------- SETTINGS 1 ----------
Gain +0
Lead Rotation Last-On
Purge Delay 1.0min
Lag Delay 0min
<More Settings>
BACK SELECT
---------- SETTINGS 2 ----------
Standby Time 7min
System Run-On 10min
Setback 10 F
Last Stage Hold 5 F
Set Time 12:05Pm
<Day/Night Schedules>
BACK SELECT
--- DAY/NIGHT SCHEDULES ---
Set Time **:**
Day Schedule **:**
Night Schedule **:**
BACK SAVE
---- MANUAL LEAD STAGE ----
A
B
C
D
E
BACK SAVE
--- AUTO ROTATE PERIOD ---
24
hrs
[ ]
BACK SAVE
--------- PURGE DELAY ---------
1.0
min
[ ]
BACK SAVE
----------- LAG DELAY -----------
0
min
[ ]
SYSTEM SETTINGS1
SYSTEM SETTINGS2
BACK SAVE
-------- STANDBY DELAY --------
7
min
[ ]
BACK SAVE
-------- SYSTEM RUN-ON --------
10
min
[ ]
BACK SAVE
-------------- SETBACK -----------
10
F
[ ]
BACK SAVE
------ LAST STAGE HOLD ------
5
F
[ ]
BACK SAVE
----- SET PRESENT TIME -----
11:**Pm
SETBACK INPUT
Shutdown
/TStat
BACK SELECT
---------- MAINTENANCE ---------
System Trim +0 F
Outdoor Trim +0 F
Soft-Off Delay 10sec
<Output Trim>
<Configuration>
MAINTENANCE
BACK SAVE
--- SYSTEM SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
-- OUTDOOR SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
------- SOFT-OFF DELAY --------
10
sec
[ ]
BACK SELECT
-------- STAGE A TRIM --------
Output Trim +0.0
<Prev Stage>
<Next Stage>
BACK SAVE
-------------- STAGE A -----------
OUTPUT TRIM
+0.0
[ ]
BACK EXIT
------ CONFIGURATION 2 ------
A=4-20ma B=0-10v
C=0-5v D=2-10v
BACK NEXT
------ CONFIGURATION 1 ------
v1.00c
Reset F
Parallel
Day/Night Schedules
All Off
BACK SAVE
-------- LEAD ROTATION -------
Manual
Time
Last-On
ALERT
DO NOT use the Output Trim for a Stage unless it is absolutely necessary. Test burner operation and modulation
output matching after adjusting the Output Trim.
Seitenansicht 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 31 32

Kommentare zu diesen Handbüchern

Keine Kommentare

Sea-doo 4-TEC GTX manuály

Uživatelské manuály a uživatelské příručky pro Motor Sea-doo 4-TEC GTX.
Poskytujeme 1 manuály pdf Sea-doo 4-TEC GTX ke stažení zdarma podle typů dokumentů: Provozní pokyny


Sea doo 4-TEC GTX Provozní pokyny (84 strany)


Značka: Sea-doo | Kategorie: Engine | Velikost: 5.00 MB |

 

Tabulka s obsahem

TABLE OF CONTENTS

2

FOREWORD

5

1. Left (port)

6

2. Right (starboard)

6

 SAFETY MEASURES

7

Maintenance

9

REGISTRATION NUMBER LOCATION

10

6-15 1 7 2-5-13

11

11 12-14

11

SOME MODELS

13

Label 13

14

Label 14

14

Label 15

14

IDENTIFICATION NUMBERS

15

INSTRUMENTS LOCATION

16

CONTROLS, COMPONENTS AND

16

INSTRUMENTS FUNCTIONS

18

WARNING

19

5) Shift Lever

20

6) Speedometer

20

7) Tachometer

21

8) Information Center

21

Gauge/Buttons

21

1. To change display mode

22

2. To set or reset a function

22

1. Repeatedly press

23

1. Press to end

23

12) Front Storage

26

Compartment Cover

26

13) Tool Kit

26

14) Air Intake Opening

27

15) Seat Strap

27

16) Seat Extension Latch

27

17) Seat Latch

27

18) Rear Grab Handle

28

19) Rear Storage Basket

28

20) Front and Rear

28

(bow/stern) Eyelets

28

27) Bilge Drain Plugs

30

28) Jet Pump Nozzle

30

29) Reverse Gate

30

1. Ski/wake board post lifted

34

2. Ensure it is locked

34

Engine Coolant

37

BREAK-IN PERIOD

39

PRE-OPERATION CHECKS

40

Water Flow in Exhaust

43

Manifold (only when

43

OPERATING INSTRUCTIONS

44

Boarding the Watercraft

47

Starting

49

Rough Water or Poor

50

Visibility Operation

50

Crossing Waves

50

Stopping/Docking

50

Beaching

50

Shutting Off the Engine

51

POST-OPERATION CARE

52

Anticorrosion Treatment

53

SPECIAL PROCEDURES

54

Towing the Watercraft in

57

Low-Charge Battery

58

Condition

58

MAINTENANCE

59

Lubrication

60

Periodic Inspection

60

Periodic Inspection Chart

61

1. Fuses

65

FUSE IDENTIFICATION

65

2. Main fuse

67

TRAILERING, STORAGE

69

AND PRESEASON PREPARATION

69

Preseason Preparation

72

TROUBLESHOOTING

74

SPECIFICATIONS

80

SI* METRIC INFORMATION

83





Další produkty a příručky pro Motor Sea-doo

Modely Typ Dokumentu
4-TEC WAKE Uživatelský manuál   WAKE™ 155, 2 stránky
2004 3D RFI Specifikace   Sea-doo 2004 3D RFI Specifications, 118 stránky
2005 3D RFI Specifikace   Sea-doo 2005 3D RFI Specifications, 123 stránky
2005 3D RFI Specifikace   Sea-doo 2005 3D RFI Specifications [en] , 117 stránky
GS Provozní pokyny   Sea-doo GS Operating instructions, 107 stránky
GS 5626 Provozní pokyny   Sea-doo GS 5626 Operating instructions, 96 stránky
LRV Provozní pokyny   Sea-doo LRV Operating instructions, 88 stránky
2001 GTI 5552 Uživatelský manuál   1988-2003 SeaDoo Specifications Booklet, 193 stránky