18 Raypak, Inc.
OUTDOOR CUTOFF TEMPERATURE
AdjustableOff,20ºF-100ºF,On Default:65ºF
Button: MENU/Set Point/Outdoor Cutoff inSetPoint
Button: MENU/Set Point/Offset/Outdoor Cutoff inReset
• If the outdoor sensor is installed, the Outdoor Cutoff screen will automatically appear after
the temperature Set Point has been selected.
• When the outdoor temperature falls to the adjustable Outdoor Cutoff temperature, the
TempTracker mod+ will control and modulate Boilers to hold the calculated temperature.
----------- SETTINGS ------------
Season Winter
Set Point 140 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
------------- SEASON --------------
Winter
Summer
BACK SAVE
------------ SET POINT ----------
140 F
[ ]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK SAVE
BACK START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK SAVE
------- OUTDOOR CUTOFF -------
65 F
[ ]
-------------- OFFSET -------------
+0 F
[ ]
BACK SAVE
--- MINIMUM WATER TEMP ----
140 F
[ ]
BACK SAVE
--- MAXIMUM WATER TEMP ----
220 F
[ ]
Reset Ratio
BACK SAVE
Shutdown or
TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120 F
[ ]
------ EMS 20ma SETPOINT-----
220 F
[ ]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK SAVE
BACK SAVE
BACK SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK SAVE
BACK SAVE
BACK SAVE
BACK EXIT
BACK NEXT
BACK SAVE
BACK SAVE
Enabled
BACK SAVE
------- DHW SETPOINT -------
180 F
[ ]
Disabled
• When the outdoor temperature rises to the Outdoor Cutoff plus a 2°F differential, the TempTracker mod+ will disable the system.
The Message Display Line will display Outdoor Cutoff.
• The Outdoor Cutoff can be set from 20°F to 100°F. In addition, the Setting can be set to ON or OFF. In the ON position, the
System Relay will run regardless of the Outdoor temperature (OD) and the burner stages will be active to hold the calculated water
temperature. (Note: The lowest water temperature the TempTracker mod+ will circulate is 70°F. If the Outdoor Cutoff is turned
ON and the Season is set to Winter, the TempTracker mod+ will circulate at least 70°F water even in the hottest of weather.) In the
OFF position, the system pump will always be off and all burner stages will be off for heating.
OFFSET
Adjustable50ºF-(-50ºF) Default:0ºF
Button: MENU/Set Point/Offset inResetonly
• The Offset setting lets you adjust the starting points of the Reset Ratio curves. This means
that, regardless of the Outdoor temperature (OD), or the Reset Ratio that has been selected,
when the Offset setting is changed, that change is directly added to or subtracted from the
calculated temperature. For example, if the Set Point temperature was 130°F and the Offset
was changed from 0° to 10° (an increase of 10°), then the Set Point temperature would
increase to 140°F
----------- SETTINGS ------------
Season Winter
Set Point 140 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
------------- SEASON --------------
Winter
Summer
BACK SAVE
------------ SET POINT ----------
140 F
[ ]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK SAVE
BACK START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK SAVE
------- OUTDOOR CUTOFF -------
65 F
[ ]
-------------- OFFSET -------------
+0 F
[ ]
BACK SAVE
--- MINIMUM WATER TEMP ----
140 F
[ ]
BACK SAVE
--- MAXIMUM WATER TEMP ----
220 F
[ ]
Reset Ratio
BACK SAVE
Shutdown or
TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120 F
[ ]
------ EMS 20ma SETPOINT-----
220 F
[ ]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK SAVE
BACK SAVE
BACK SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK SAVE
BACK SAVE
BACK SAVE
BACK EXIT
BACK NEXT
BACK SAVE
BACK SAVE
Enabled
BACK SAVE
------- DHW SETPOINT -------
180 F
[ ]
Disabled
• The Offset setting does not change the ratio selection. For instance, with 1.00 (OD):1.00 (SYS) Reset Ratio, the System water
temperature (SYS) will always increase one degree for each degree change in the Outdoor temperature (OD). What the Offset does
is add or subtract a constant temperature value. (See Understanding Operation Concept on page 5)
• If required: AdjusttheWaterOffsetinmildweather. If the ambient building temperatures are too warm in the mild weather,
decrease the Water Offset. If the ambient building temperatures are too cold in the mild weather, increase the Water Offset. The
rule of thumb for baseboard radiation is to change the Offset 4°F for every 1°F you wish to change the building temperatures. In
radiant heat applications, change the Offset 1°F or 2°F for every 1°F you wish to change the building temperature.
MINIMUM WATER TEMP
Adjustable70ºF-180ºF Default:120ºF
Button: MENU/Set Point/Offset/Outdoor Cutoff/Minimum Water Temp inResetonly
• The Minimum Water Temperature must be set to the boiler manufacturer’s specication.
The TempTracker mod+ will calculate the Set Point based on the Outdoor temperature
(OD), the Reset Ratio, and the Offset value. The TempTracker mod+ will control all boilers
modulation to hold either the Set Point temperature, or the Minimum Water Temperature,
whichever is higher.
• The Minimum Water Temperature must be at least 20°F lower than the Maximum
Temperature (See next setting).
----------- SETTINGS ------------
Season Winter
Set Point 140 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
------------- SEASON --------------
Winter
Summer
BACK SAVE
------------ SET POINT ----------
140 F
[ ]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK SAVE
BACK START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK SAVE
------- OUTDOOR CUTOFF -------
65 F
[ ]
-------------- OFFSET -------------
+0 F
[ ]
BACK SAVE
--- MINIMUM WATER TEMP ----
140 F
[ ]
BACK SAVE
--- MAXIMUM WATER TEMP ----
220 F
[ ]
Reset Ratio
BACK SAVE
Shutdown or
TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120 F
[ ]
------ EMS 20ma SETPOINT-----
220 F
[ ]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK SAVE
BACK SAVE
BACK SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK SAVE
BACK SAVE
BACK SAVE
BACK EXIT
BACK NEXT
BACK SAVE
BACK SAVE
Enabled
BACK SAVE
------- DHW SETPOINT -------
180 F
[ ]
Disabled
MAXIMUM WATER TEMP
Adjustable90ºF-240ºF Default:240ºF
Button: MENU/Set Point/Offset/..../Maximum Water Temperature inResetonly
• This is the highest temperature heating water the TempTracker mod+ will circulate through
the heating system. It is available in Reset mode only.
• When using a radiation system, it should be set according to the tubing or oor
manufacturer’s specication.
• The Maximum Temperature must be at least 20°F higher than the Minimum Temperature.
----------- SETTINGS ------------
Season Winter
Set Point 140 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
------------- SEASON --------------
Winter
Summer
BACK SAVE
------------ SET POINT ----------
140 F
[ ]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK SAVE
BACK START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK SAVE
------- OUTDOOR CUTOFF -------
65 F
[ ]
-------------- OFFSET -------------
+0 F
[ ]
BACK SAVE
--- MINIMUM WATER TEMP ----
140 F
[ ]
BACK SAVE
--- MAXIMUM WATER TEMP ----
220 F
[ ]
Reset Ratio
BACK SAVE
Shutdown or
TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120 F
[ ]
------ EMS 20ma SETPOINT-----
220 F
[ ]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK SAVE
BACK SAVE
BACK SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK SAVE
BACK SAVE
BACK SAVE
BACK EXIT
BACK NEXT
BACK SAVE
BACK SAVE
Enabled
BACK SAVE
------- DHW SETPOINT -------
180 F
[ ]
Disabled