TempTracker mod+ & TempTracker mod+ Extension Installation Manual 19
SYSTEM SETTINGS
Button: MENU/<System Settings>
The Settings 1 and Settings 2 menus provide access to adjusting and ne-tuning the system for
enhanced comfort and more fuel savings. The TempTracker mod+ behaves differently based
on the selected Control Modes (see Startup Settings on page 14).
----------- SETTINGS ------------
Season Winter
Set Point 70 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
---------------- GAIN --------------
+0
F
[ ]
BACK SELECT
---------- SETTINGS 1 ----------
Gain +0
Lead Rotation Last-On
Purge Delay 1.0min
Lag Delay 0min
<More Settings>
BACK SELECT
---------- SETTINGS 2 ----------
Standby Time 7min
System Run-On 10min
Setback 10 F
Last Stage Hold 5 F
Set Time 12:05Pm
<Day/Night Schedules>
BACK SELECT
--- DAY/NIGHT SCHEDULES ---
Set Time **:**
Day Schedule **:**
Night Schedule **:**
BACK SAVE
---- MANUAL LEAD STAGE ----
A
B
C
D
E
BACK SAVE
--- AUTO ROTATE PERIOD ---
24
hrs
[ ]
BACK SAVE
--------- PURGE DELAY ---------
1.0
min
[ ]
BACK SAVE
----------- LAG DELAY -----------
0
min
[ ]
SYSTEM SETTINGS1
SYSTEM SETTINGS2
BACK SAVE
-------- STANDBY DELAY --------
7
min
[ ]
BACK SAVE
-------- SYSTEM RUN-ON --------
10
min
[ ]
BACK SAVE
-------------- SETBACK -----------
10
F
[ ]
BACK SAVE
------ LAST STAGE HOLD ------
5
F
[ ]
BACK SAVE
----- SET PRESENT TIME -----
11:**Pm
SETBACK INPUT
Shutdown
/TStat
BACK SELECT
---------- MAINTENANCE ---------
System Trim +0 F
Outdoor Trim +0 F
Soft-Off Delay 10sec
<Output Trim>
<Configuration>
MAINTENANCE
BACK SAVE
--- SYSTEM SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
-- OUTDOOR SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
------- SOFT-OFF DELAY --------
10
sec
[ ]
BACK SELECT
-------- STAGE A TRIM --------
Output Trim +0.0
<Prev Stage>
<Next Stage>
BACK SAVE
-------------- STAGE A -----------
OUTPUT TRIM
+0.0
[ ]
BACK EXIT
------ CONFIGURATION 2 ------
A=4-20ma B=0-10v
C=0-5v D=2-10v
BACK NEXT
------ CONFIGURATION 1 ------
v1.00c
Reset F
Parallel
Day/Night Schedules
All Off
BACK SAVE
-------- LEAD ROTATION -------
Manual
Time
Last-On
----------- SETTINGS ------------
Season Winter
Set Point 70 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
---------------- GAIN --------------
+0
F
[ ]
BACK SELECT
---------- SETTINGS 1 ----------
Gain +0
Lead Rotation Last-On
Purge Delay 1.0min
Lag Delay 0min
<More Settings>
BACK SELECT
---------- SETTINGS 2 ----------
Standby Time 7min
System Run-On 10min
Setback 10 F
Last Stage Hold 5 F
Set Time 12:05Pm
<Day/Night Schedules>
BACK SELECT
--- DAY/NIGHT SCHEDULES ---
Set Time **:**
Day Schedule **:**
Night Schedule **:**
BACK SAVE
---- MANUAL LEAD STAGE ----
A
B
C
D
E
BACK SAVE
--- AUTO ROTATE PERIOD ---
24
hrs
[ ]
BACK SAVE
--------- PURGE DELAY ---------
1.0
min
[ ]
BACK SAVE
----------- LAG DELAY -----------
0
min
[ ]
SYSTEM SETTINGS1
SYSTEM SETTINGS2
BACK SAVE
-------- STANDBY DELAY --------
7
min
[ ]
BACK SAVE
-------- SYSTEM RUN-ON --------
10
min
[ ]
BACK SAVE
-------------- SETBACK -----------
10
F
[ ]
BACK SAVE
------ LAST STAGE HOLD ------
5
F
[ ]
BACK SAVE
----- SET PRESENT TIME -----
11:**Pm
SETBACK INPUT
Shutdown
/TStat
BACK SELECT
---------- MAINTENANCE ---------
System Trim +0 F
Outdoor Trim +0 F
Soft-Off Delay 10sec
<Output Trim>
<Configuration>
MAINTENANCE
BACK SAVE
--- SYSTEM SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
-- OUTDOOR SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
------- SOFT-OFF DELAY --------
10
sec
[ ]
BACK SELECT
-------- STAGE A TRIM --------
Output Trim +0.0
<Prev Stage>
<Next Stage>
BACK SAVE
-------------- STAGE A -----------
OUTPUT TRIM
+0.0
[ ]
BACK EXIT
------ CONFIGURATION 2 ------
A=4-20ma B=0-10v
C=0-5v D=2-10v
BACK NEXT
------ CONFIGURATION 1 ------
v1.00c
Reset F
Parallel
Day/Night Schedules
All Off
BACK SAVE
-------- LEAD ROTATION -------
Manual
Time
Last-On
--------
SYSTEM
A
B
C
D
1
2
RUNPROGRAM
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7
8
9
10
11
12
13
15
14
17
16
18
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
+
mA
22
-
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
PROVE
/DHW
SHUTDOWN
/SETBACK
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 30VA MAX
INPUT RATINGS:
USE COPPER WIRE,
CLASS 1 WIRE ONLY.
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
CAUTION
: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
Gain
Lead Rotation
Purge Delay
Lag Delay
Standby Time
System Run-On
Setback
Last Stage Hold
Day/Night Schedules
ALERT
To be able to change the TempTracker mod+ settings the Program/Run
Switch must be set to Program. The switch is located under the Enclosure
Wiring Cover for security. The Enclosure Wiring Cover can be securely
closed using a lock.
GAIN
Adjustable-10to+10 Default:0
Button: MENU/<System Settings>/Gain
The Gain adjusts the aggressiveness of the TempTracker mod+ PID logic to control how
much modulation is changed when the system temperature is different from the Set Point.
A Gain of 0 is a good starting point for all systems.
If during normal load conditions, the system temperature tends to uctuate signicantly,
decrease the Gain by two numbers (for example, from 0 to -2). Wait for at least 15 minutes
before evaluating how the change has affected the system.
If, during normal load conditions the system temperature tends to remain consistently below
the Set Point (or consistently above the Set Point), increase the Gain by two numbers (for
example, from 0 to 2). Wait for at least 15 minutes before evaluating how the change has
affected the system.
----------- SETTINGS ------------
Season Winter
Set Point 70 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
---------------- GAIN --------------
+0
F
[ ]
BACK SELECT
---------- SETTINGS 1 ----------
Gain +0
Lead Rotation Last-On
Purge Delay 1.0min
Lag Delay 0min
<More Settings>
BACK SELECT
---------- SETTINGS 2 ----------
Standby Time 7min
System Run-On 10min
Setback 10 F
Last Stage Hold 5 F
Set Time 12:05Pm
<Day/Night Schedules>
BACK SELECT
--- DAY/NIGHT SCHEDULES ---
Set Time **:**
Day Schedule **:**
Night Schedule **:**
BACK SAVE
---- MANUAL LEAD STAGE ----
A
B
C
D
E
BACK SAVE
--- AUTO ROTATE PERIOD ---
24
hrs
[ ]
BACK SAVE
--------- PURGE DELAY ---------
1.0
min
[ ]
BACK SAVE
----------- LAG DELAY -----------
0
min
[ ]
SYSTEM SETTINGS1
SYSTEM SETTINGS2
BACK SAVE
-------- STANDBY DELAY --------
7
min
[ ]
BACK SAVE
-------- SYSTEM RUN-ON --------
10
min
[ ]
BACK SAVE
-------------- SETBACK -----------
10
F
[ ]
BACK SAVE
------ LAST STAGE HOLD ------
5
F
[ ]
BACK SAVE
----- SET PRESENT TIME -----
11:**Pm
SETBACK INPUT
Shutdown
/TStat
BACK SELECT
---------- MAINTENANCE ---------
System Trim +0 F
Outdoor Trim +0 F
Soft-Off Delay 10sec
<Output Trim>
<Configuration>
MAINTENANCE
BACK SAVE
--- SYSTEM SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
-- OUTDOOR SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
------- SOFT-OFF DELAY --------
10
sec
[ ]
BACK SELECT
-------- STAGE A TRIM --------
Output Trim +0.0
<Prev Stage>
<Next Stage>
BACK SAVE
-------------- STAGE A -----------
OUTPUT TRIM
+0.0
[ ]
BACK EXIT
------ CONFIGURATION 2 ------
A=4-20ma B=0-10v
C=0-5v D=2-10v
BACK NEXT
------ CONFIGURATION 1 ------
v1.00c
Reset F
Parallel
Day/Night Schedules
All Off
BACK SAVE
-------- LEAD ROTATION -------
Manual
Time
Last-On
----------- SETTINGS ------------
Season Winter
Set Point 70 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
---------------- GAIN --------------
+0
F
[ ]
BACK SELECT
---------- SETTINGS 1 ----------
Gain +0
Lead Rotation Last-On
Purge Delay 1.0min
Lag Delay 0min
<More Settings>
BACK SELECT
---------- SETTINGS 2 ----------
Standby Time 7min
System Run-On 10min
Setback 10 F
Last Stage Hold 5 F
Set Time 12:05Pm
<Day/Night Schedules>
BACK SELECT
--- DAY/NIGHT SCHEDULES ---
Set Time **:**
Day Schedule **:**
Night Schedule **:**
BACK SAVE
---- MANUAL LEAD STAGE ----
A
B
C
D
E
BACK SAVE
--- AUTO ROTATE PERIOD ---
24
hrs
[ ]
BACK SAVE
--------- PURGE DELAY ---------
1.0
min
[ ]
BACK SAVE
----------- LAG DELAY -----------
0
min
[ ]
SYSTEM SETTINGS1
SYSTEM SETTINGS2
BACK SAVE
-------- STANDBY DELAY --------
7
min
[ ]
BACK SAVE
-------- SYSTEM RUN-ON --------
10
min
[ ]
BACK SAVE
-------------- SETBACK -----------
10
F
[ ]
BACK SAVE
------ LAST STAGE HOLD ------
5
F
[ ]
BACK SAVE
----- SET PRESENT TIME -----
11:**Pm
SETBACK INPUT
Shutdown
/TStat
BACK SELECT
---------- MAINTENANCE ---------
System Trim +0 F
Outdoor Trim +0 F
Soft-Off Delay 10sec
<Output Trim>
<Configuration>
MAINTENANCE
BACK SAVE
--- SYSTEM SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
-- OUTDOOR SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
------- SOFT-OFF DELAY --------
10
sec
[ ]
BACK SELECT
-------- STAGE A TRIM --------
Output Trim +0.0
<Prev Stage>
<Next Stage>
BACK SAVE
-------------- STAGE A -----------
OUTPUT TRIM
+0.0
[ ]
BACK EXIT
------ CONFIGURATION 2 ------
A=4-20ma B=0-10v
C=0-5v D=2-10v
BACK NEXT
------ CONFIGURATION 1 ------
v1.00c
Reset F
Parallel
Day/Night Schedules
All Off
BACK SAVE
-------- LEAD ROTATION -------
Manual
Time
Last-On
LEAD BOILER ROTATION
AdjustableManual,Time(1hrto60Days),Last-On Default:Last-On
Button: MENU/<System Settings>/Lead Rotation
The Lead Boiler is the rst boiler brought on when output is required.
The Lead Boiler can be rotated automatically, manually or based on Last-On. The Last-On
rotation is recommended.
The current Lead Boiler is shown in brackets on the main display.
Only Boilers which are set to Auto Mode can be Lead. Therefore, not all the Boilers may be
available when manually selecting a new Lead Boiler.
PURGE DELAY
Adjustable1.0minto10.0min Default:1.0min
Button: MENU/<System Settings>/Purge Delay
Many boilers go through a purge cycle before they are brought on line.
When the TempTracker mod+ activates a boiler, it does not start to calculate its output until
the Purge Delay is over. This allows the boiler to fully come on line and begin producing
output.
The Purge Delay helps to prevent short cycling of a newly activated burner. Once the
burner is activated, it MUST run through the entire Purge Delay period.
The minimum Purge Delay setting MUST be set to the time required by the boiler
manufacturer. Time entry is in 0.1 of a minute (i.e. 1.5min will equal 90 seconds.)
The Message Display Line will display Purge Delay and the amount of time remaining in
the purge.
----------- SETTINGS ------------
Season Winter
Set Point 70 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
---------------- GAIN --------------
+0
F
[ ]
BACK SELECT
---------- SETTINGS 1 ----------
Gain +0
Lead Rotation Last-On
Purge Delay 1.0min
Lag Delay 0min
<More Settings>
BACK SELECT
---------- SETTINGS 2 ----------
Standby Time 7min
System Run-On 10min
Setback 10 F
Last Stage Hold 5 F
Set Time 12:05Pm
<Day/Night Schedules>
BACK SELECT
--- DAY/NIGHT SCHEDULES ---
Set Time **:**
Day Schedule **:**
Night Schedule **:**
BACK SAVE
---- MANUAL LEAD STAGE ----
A
B
C
D
E
BACK SAVE
--- AUTO ROTATE PERIOD ---
24
hrs
[ ]
BACK SAVE
--------- PURGE DELAY ---------
1.0
min
[ ]
BACK SAVE
----------- LAG DELAY -----------
0
min
[ ]
SYSTEM SETTINGS1
SYSTEM SETTINGS2
BACK SAVE
-------- STANDBY DELAY --------
7
min
[ ]
BACK SAVE
-------- SYSTEM RUN-ON --------
10
min
[ ]
BACK SAVE
-------------- SETBACK -----------
10
F
[ ]
BACK SAVE
------ LAST STAGE HOLD ------
5
F
[ ]
BACK SAVE
----- SET PRESENT TIME -----
11:**Pm
SETBACK INPUT
Shutdown
/TStat
BACK SELECT
---------- MAINTENANCE ---------
System Trim +0 F
Outdoor Trim +0 F
Soft-Off Delay 10sec
<Output Trim>
<Configuration>
MAINTENANCE
BACK SAVE
--- SYSTEM SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
-- OUTDOOR SENSOR TRIM ----
+0
F
[ ]
BACK SAVE
------- SOFT-OFF DELAY --------
10
sec
[ ]
BACK SELECT
-------- STAGE A TRIM --------
Output Trim +0.0
<Prev Stage>
<Next Stage>
BACK SAVE
-------------- STAGE A -----------
OUTPUT TRIM
+0.0
[ ]
BACK EXIT
------ CONFIGURATION 2 ------
A=4-20ma B=0-10v
C=0-5v D=2-10v
BACK NEXT
------ CONFIGURATION 1 ------
v1.00c
Reset F
Parallel
Day/Night Schedules
All Off
BACK SAVE
-------- LEAD ROTATION -------
Manual
Time
Last-On
ALERT
Set Purge Delay as per boiler
manufacturer recommendation.