SENSOR FAULT
AllOff,AllOn Default:AllOn
Button: MENU/<System Startup>/..../Sensor Fault
The Sensor Fault will determine the operating status of all output stages that are set to Auto
when a sensor reads Short or Open.
----------- SETTINGS ------------
Season Winter
Set Point 140 F
<System Settings>
<Maintenance>
<Histories>
<System Startup>
BACK SELECT
BACK SAVE
------------- SEASON --------------
Winter
Summer
BACK SAVE
------------ SET POINT ----------
140 F
[ ]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK SAVE
BACK START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK SAVE
------- OUTDOOR CUTOFF -------
65 F
[ ]
-------------- OFFSET -------------
+0 F
[ ]
BACK SAVE
--- MINIMUM WATER TEMP ----
140 F
[ ]
BACK SAVE
--- MAXIMUM WATER TEMP ----
220 F
[ ]
Reset Ratio
BACK SAVE
Shutdown or
TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120 F
[ ]
------ EMS 20ma SETPOINT-----
220 F
[ ]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK SAVE
BACK SAVE
BACK SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK SAVE
BACK SAVE
BACK SAVE
BACK EXIT
BACK NEXT
BACK SAVE
BACK SAVE
Enabled
BACK SAVE
------- DHW SETPOINT -------
180 F
[ ]
Disabled
RESET MODE
When All-On is selected, the TempTracker mod+ will turn all boilers On to a 100% when System reads Short or Open and Outdoor
is below Outdoor Cutoff. When Outdoor reads Short or Open, the TempTracker mod+ will turn all boilers On to a 100%.
When All-Off is selected, the TempTracker mod+ will turn all boilers Off when either System or Outdoor sensor reads Short or
Open.
SET POINT MODE
When All-On is selected, the TempTracker mod+ will turn all boilers On to a 100% when the System sensor reads Short or Open.
When All-Off is selected, the TempTracker mod+ will turn all boilers Off when the System sensor reads Short or Open.
The Outdoor Sensor Short or Open status will not affect the control operation in Set Point mode.
SETTING THE CONTROL TO FACTORY DEFAULTS
To Reset the TempTracker mod+ control to its original factory defaults, power down the
control. Hold down the two right most buttons while powering the control back up until the
Total Clear Started screen appears. The Display will direct you to the Startup
menu to program the control after the defaults are loaded.
TOTAL CLEAR STARTED
Release buttons
and
Please Wait
NOTE: When resetting the control to original factory defaults all control settings will be overwritten and will no longer exist.
ALERT
Do not turn off power to control until all Startup settings have been made. Otherwise, the next
power-up will be set to many Startup factory settings that might not t your application.