OPERATING AND
INSTALLATION
INSTRUCTIONS
Models 122-322
Type H, WH, & P
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids or other combustible materials in the vicinity of
this or any other appliance. To do so may result in an explosion or fire.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage,
personal injury or loss of life. Refer to this manual. Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS:
· Do not try to light any appliance.
· Do not touch any electrical switch; do not use any phone in your building.
· Immediately call your gas supplier from a neighbors phone. Follow the gas suppliers instructions.
· If you cannot reach your gas supplier, call the fire department.
This manual should be maintained in legible
condition and kept adjacent to the heater or
in a safe place for future reference.
P/N 241112
CATALOG NO. 1000.53F
Effective: 03-01-05
Replaces: 10-01-03
Seitenansicht 0
1 2 3 4 5 6 ... 55 56

Inhaltsverzeichnis

Seite 1 - INSTRUCTIONS

OPERATING ANDINSTALLATIONINSTRUCTIONSModels 122-322Type H, WH, & PFOR YOUR SAFETYDo not store or use gasoline or other flammable vapors and liquid

Seite 2 - TABLE OF CONTENTS

OUTDOOR INSTALLATIONSRaypak Hi Delta Heaters are design certified for outdoor installation. Heaters must not be installed under an overhang thatis les

Seite 3

SECTION C: COMBUSTION AND VENTILATION AIRCOMBUSTION AND VENTILATION AIR (Indoor Units)The heater must be supplied with sufficient quantities of non-co

Seite 4

COMBUSTION AND VENTILATION AIR SUPPLY (FOR CANADA INSTALLATION)CAUTION: All combustion air has to be drawn from the air outside the building (the mech

Seite 5

SECTION D: WATER PIPING - GENERALThe heater should be located so that any water leaks will not cause damage to the adjacent area or structures.CAUTION

Seite 6 - HI DELTA COMPONENT LOCATION

SECTION E: HYDRONIC HEATING PIPINGPUMP SELECTIONIn order to ensure proper performance of your boiler system, you must install a properly sized pump. R

Seite 7 - General Information

SINGLE BOILER - LOW TEMPERATURE APPLICATION (HEAT PUMP) PRIMARY/SECONDARY PIPINGDUAL BOILER PRIMARY/SECONDARY PIPING15

Seite 8

SECTION F: DOMESTIC HOT WATER PIPINGWhen designing the water piping system for domestic water applications, water hardness should be considered. Table

Seite 9 - CLEARANCES

17SINGLE HEATER DOMESTIC HOT WATER WITH ONE STORAGE TANK

Seite 10 - Fig # 9400

SECTION G: POOL HEATINGCAUTIOCAUTION: Power to the heater should be interlocked with the main system pump to make sure the heater does not firewithout

Seite 11

SECTION H: GAS SUPPLY CONNECTIONSDANGER: Make sure the gas on which the heater will operate is the same type as specified on the heater model andratin

Seite 12

TABLE OF CONTENTSPAGENO. 4 SECTION A: BEFORE INSTALLING THE HEATER 8 SECTION B: HEATER INSTALLATION11 SECTION C: COMBUSTION AND VENTILATION AIR13 SE

Seite 13

GAS PRESSURE REGULATORThe gas valve pressure regulator(s) on the heater are nominally preset at 3.5" W.C. for Natural gas, and 10.5" W.C. fo

Seite 14

CIRCUITBREAKERWHITEGROUNDBLACKGREENABCVOLT-OHMMETERSECTION I: ELECTRICAL POWER CONNECTIONSInstallations must follow these codes:· National Electrical

Seite 15

MAKING THE ELECTRICAL CONNECTIONSRefer to Fig. #9403 Wiring Connection, and Wiring Diagram #152564.1. Verify circuit breaker is properly sized by refe

Seite 16

ELECTRICAL CONNECTIONS - DOMESTIC HOT WATERCAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper

Seite 17

SECTION J: VENTING CONNECTIONSGENERALCAUTION: Proper installation of flue exhaust venting is critical for the safe and efficient operation of the heat

Seite 18 - SECTION G: POOL HEATING

Category Determination for Venting Purpose and Venting Arrangement25TABLE J-1* As defined in the latest edition of the NFGC, or in Canada, the B149.1

Seite 19 - Fig. #9401.1

Support of Vent StackThe weight of the vent stack or chimney must not rest on the heater vent connection. Support must be provided incompliance with a

Seite 20

Venting Installation TipsSupport piping:· horizontal runs- at least every five (5) feet.· vertical runs - use braces:· under or near elbowsFollow item

Seite 21 - Fig. # 9237

28SECTION J-1 Natural Draft Vertical Venting (Category I)NATURAL DRAFT VERTICAL VENTNOTE:**Vent lengths are based on a lateral length of 2 feet. Refe

Seite 22 - Fig. #9446

• Natural Draft Vertical Venting System InstallationNatural draft venting uses the natural buoyancy of the heated flue products to create a thermal d

Seite 23 - Fig. #9138.2

DANGER: Make sure the gas on which the heater will operate is the same type as that specifiedon the heater model and rating plate.WARNING: Should over

Seite 24

Common venting systems may be too large when an existing unit is removed. At the time of removal of an existing appliance,the following steps must be

Seite 25 - TABLE J-1

SECTION J-2 Horizontal Thru-Wall Venting (Category III)HORIZONTAL THRU-WALL VENTING (CATEGORY III) TABLE• Horizontal Thru-wall Venting System (Categor

Seite 26

The total length of the horizontal thru-wall exhaust vent system should not exceed seventy (70) feet in length. If horizontalrun exceeds 70 feet, an

Seite 27 - Venting Installation Tips

DIRECT VENTHorizontal Thru-wall Venting(Category III)HORIZONTAL THRU-WALL VENTING TABLE33SECTION J-3

Seite 28 - NATURAL DRAFT VERTICAL VENT

• Horizontal Thru-wall Direct Vent System (Category III) InstallationThese installations utilize the heater mounted blower to draw combustion air fro

Seite 29

DIRECT VENTVertical Venting (Category I)VERTICAL VENTING TABLE35SECTION J-4

Seite 30

• Vertical Direct Vent System InstallationThese installations utilize the heater mounted blower to draw combustion air from outdoors and uses the natu

Seite 31 - Fig # 9402

SECTION J-5 Outdoor InstallationOutdoor models are self-venting when installed with the factory-supplied restricted direct vent cap and require no a

Seite 32

SECTION K: CONTROLSWARNING: Installation, adjustment and service of heater controls including timing of various operating functions must be performed

Seite 33 - SECTION J-3

IGNITION MODULEFig. J-3MANUAL RESET HIGH LIMITFig. J-4FLOW SWITCHTHERMOSTAT CONTROLIGNITION CONTROL MODULEThe interrupted proved ignition devic

Seite 34

Pay attention to these terms:DANGER: indicates the presence of immediate hazards which will cause severe personal injury, deathor substantial property

Seite 35

LOW WATER CUT OFF (OPTIONAL)The low water cut off automatically shuts down the burner wheneverwater level drops below the level of the sensing probe.

Seite 36

41WIRE DIAGRAM MODELS 122-322Reference Drawing Number M152564C

Seite 37

SECTION L: GENERAL SAFETY PRECAUTIONSTo meet commercial water use needs, the temperature Hi-Limt on this hot water heater is adjustable up to 210°F. H

Seite 38 - SECTION K: CONTROLS

SECTION M: PRE-START-UPFILLING SYSTEM-HEATING HEATERSFill system with water. Purge all air from the system using purge valve sequence. After syste

Seite 39

SECTION N: INITIAL START-UP1.0 TOOLS NEEDED• One 12-0-12, 24” scale manometer• Two 6-0-6, 12” scale manometers• 7/16” open end wrench• 1/2” open e

Seite 40 - Drw. #8996.1

3.0 START-UP3.1 Blower Adjustment1. Disconnect fan pressure switch tubing at plenum and connect manometer using a tee.2. Close all manual firing valve

Seite 41 - WIRE DIAGRAM MODELS 122-322

SECTION O: POST START-UP CHECKCheck off steps as completed:1. Heater and heat distribution units or storage tank filled with water?2. Automatic air

Seite 42 - Adjustment

SECTION P: OPERATIONOPERATING INSTRUCTIONSLighting Instructions1. STOP! Read the safety information first.2. Set the thermostat to the lowest settin

Seite 43 - SECTION M: PRE-START-UP

SECTION Q: MAINTENANCESUGGESTED MINIMUM MAINTENANCE SCHEDULE:Regular service by a qualified service agency and maintenance must be performed to ensu

Seite 44 - SECTION N: INITIAL START-UP

APPENDIX AINSIDE COMBUSTION AIR CONTAMINATION:All heaters experience some condensation during start-up.The condensate from flue gas is slightly acid

Seite 45

MODEL IDENTIFICATIONThe model identification number and heater serial number are found on the heater data plate located on the left inside jacketof t

Seite 46

Fig # 24109350

Seite 47 - SECTION P: OPERATION

51HEAT EXCHANGER DETAIL

Seite 51 - HEAT EXCHANGER DETAIL

LIMITED PARTS WARRANTY COMMERCIAL HEATERSTYPE HI DELTA MODELS 122 TO 322MODELS H AND WHSCOPE:Raypak, Inc. (“Raypak”) warrants to the original owner th

Seite 52

Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 • (805) 278-5300 • Fax (800) 872-9725Raypak Canada LTD, 2805 Slough Street, Mississauga, Ontario,

Seite 53

HI DELTA COMPONENT LOCATION6BACKLEFT-SIDEFRONT(See detail page 7)(See detail page 7)

Seite 54

7General InformationGas Valve Detail Air Shutter Adjustment

Seite 55

SECTION B: HEATER INSTALLATIONINSTALLATION CODESInstallations must follow these codes:· Local, state, provincial, and national codes, laws, regulation

Seite 56 - Litho in U. S. A

CLEARANCESTABLE 1INDOOR INSTALLATIONMINIMUM CLEARANCES FROM COMBUSTIBLE SURFACESModelsHeater Side 122-322Floor See Note 1Rear 1"Water Side 12”Oth

Kommentare zu diesen Handbüchern

Keine Kommentare