ELECTRONIC BOILERSEQUENCER & OUTDOORRESET CONTROLLERInstallation and Operating InstructionsCatalog No: 5000.54HEffective: 06-19-07Replaces: 02-01-

Seite 2

WATER TEMPERATURE SENSOR INSTALLATIONHYDRONIC INSTALLATIONS Fig. #9496TYPICAL WATER SENSOR• The water sensor should be installed in the system sup

Seite 3 - TABLE OF CONTENTS

Air temperature sensor must be installed across air temperature sensor contacts. The sensor is not activated and can beleft stored in controller encl

Seite 4 - IMPORTANT SAFETY INSTRUCTIONS

121. Install the air temperature sensor across the air temperature sensor contacts (P2, pins 1 and 2; see the fieldwiring diagram on pg. 13).2. On the

Seite 5 - INTRODUCTION

FIELD WIRINGSingle-Stage (On/Off) Boilers- All stage connections on the controlboard are connected at the {TH}(Thermostat) location on theboiler wirin

Seite 6 - • Adjustment Knobs:

INSTALLATION VERIFICATION PROCEDUREREGISTERBefore proceeding any further, please verify that the user registration form has been completed and mailed.

Seite 7 - INSTALLATION AND MOUNTING

CONTROL FAMILIARIZATIONThe System is configured using the circuit board jumpers and switches, and the front panel control potentiometers.Open the fron

Seite 8 - VOLT-OHM

16SEQUENCE OF OPERATION1. When the reset is enabled, the Y-Series Control continously monitors outdoor temperature using the outdoortemperature sensor

Seite 9 - AIR TEMPERATURE SENSOR

17Panel with Clock & LCDY-5 Configuration ShownY–SERIES ELECTRONIC BOILER CONTROL MODULENight SetpointOptionDigital DisplayOption

Seite 10 - Fig. #9496

PUMPCALL FOR HEATCONTROLONSETTINGERRORSENSORERRORINDICATOR LIGHTSSTAGE INDICATORSThe pump driver and each of the output stages' drivers has its o

Seite 11 - Fig. # 9497.1

RESET RATIOThe Reset Ratio setting determines how much the Target Temperature will increase as theoutdoor temperature drops. The Reset Ratio is expre

Seite 12 - Fig. # 9499

Y–SERIES ELECTRONIC BOILER CONTROLInstallation and Operating Instructions is a registered trademark of Underwriters Laboratories Inc.® is a

Seite 13 - FIELD WIRING

RESET RATIO CHART20PUMP TURN-OFF DELAYThe Pump Turnoff Delay works in conjunction with the Outdoor Cutoff Temperature.The Pump Turnoff Delay sets the

Seite 14 - POWER TEST

BOILER TURN-ON DELAYIn a multiple boiler system:The Boiler Turn-On Delay sets the time delay before each additional boiler is turned on inresponse to

Seite 15 - CONTROL FAMILIARIZATION

22MAXIMUM WATER TEMPERATUREThe Maximum Output Temperature is the system output high limit. This potentiometersets the maximum value the Target Temper

Seite 16 - MANUAL OVERRIDE

CIRCUIT BOARD23S5 MANUAL BYPASSSWITCHS4 MANUAL LEAD/LAGSELECTORSWITCHS2 FIRST STAGESELECTOR I.D.MAINTENANCEPLUG TEST J2 LAST STAGESELECTORJUMPERS1 SYS

Seite 17 - Y-5 Configuration Shown

INTERIOR JUMPER & SWITCHES24Fig # 9242Fig # 9245Fig # 9246S-3J-2The Last Stage Selector Jumper (J2) is comprised of an eight (8) position jumper

Seite 18

25Fig # 9244Fig # 9243Fig # 9247MANUAL LEAD-LAGThe Lead-lag Selector Switch (S4) is a ten (10) position rotary switch. Switch positions0 and 9 are no

Seite 19 - Suggested Settings

26OperationalOverride SwitchClockAlternateSetpoint AdjustmentDigital DisplayOPTIONAL ALTERNATE SETPOINT OPERATIONThe Optional Alternate Setpoint can b

Seite 20 - RESET RATIO CHART

3-C1-C2-C1-S5-S4-S6-S3-S5-S2-S2-N1-N27CALL OUT1-C2-C3-C1-S2-S3-S4-S5-S6-S1-N2-NDESCRIPTIONPC Board StandardPC Board w/ Night Set BackProgrammed EpromP

Seite 21

SYSTEM START-UP SETTINGSSYSTEM SETTING ENTERED ON DATE:Front panel control potentiometers (knobs)Reset Ratio: ______ Control Band: ______Default Value

Seite 22

TEMP Deg F 405060708090100110120Resistance (K) 26.11 19.90 15.31 11.88 9.30 7.33 5.83 4.66 3.76TEMP

Seite 23

TABLE OF CONTENTSContents PageBasics 4Important Safety Instructions 4Introduction 5Concept of Operation 5Optional Configurations 5Control Fe

Seite 24 - Fig # 9246

LIMITED WARRANTYB6000, Y-Series, E-4 & AccessoriesSCOPE OF WARRANTYRaypak, Inc. ("Raypak") warrants to the original owner the Control

Seite 25 - Fig # 9247

Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (800) 872-9725Raypak Canada Limited, 2805 Slough St., Mississauga, Ontario, Ca

Seite 26 - OPTIONAL CONTROLS

BASICS ContentsItem QuantityY–Series Boiler Control, Installed on Boiler(s) As OrderedOutdoor Temperature Sensor A

Seite 27 - REPLACEMENT PARTS LIST

Thank you for selecting the Raypak Y–Series Electronic Boiler Control. It is our sincere hope that you will enjoy itsoutstanding design, ease of use

Seite 28 - SYSTEM START-UP SETTINGS

CONTROL FEATURESThe Y-Series sequence panel includes:• Standard Indicator Lights:Stages 1 to 8: Red, indicates which stages are turned on.Pump: Green,

Seite 29 - TROUBLESHOOTING GUIDE

7INSTALLATION AND MOUNTINGIf the Y–Series Electronic Boiler Control was not mounted on the boiler by the factory, care should be taken to select asuit

Seite 30

CIRCUITBREAKERWHITEGROUNDBLACKGREENABCVOLT-OHMMETERCHECK YOUR POWER SOURCEUsing a volt-ohm meter, check the following voltages at the circuit breaker

Seite 31 - Litho in U.S.A

AIR TEMPERATURE SENSORFig. #9040OUTDOOR AIR TEMPERATURE SENSOROutdoor Air Temperature Sensor Installation Notes:• Locate the sensor on the coldest sid