TempTracker mod+ Hybrid Installation and Operation Manual 27
HTC# 059105-00D

--------SETTINGS----
Season Winter
SystemTarget140
o
F
<SystemSettings>
<Maintenance>
<SystemStartup>
BACKSELECT
--AREYOUSURE?--
No
Yes
BACKSAVE
---BACNETMODE---
Disable
Enable
BACKSAVE
-BACNETBAUDRATE-
9600
19200
38400
BACKSAVE
----MS/TPADDRESS----
64
[ ]
BACKSAVE
----BACNETID----
477000
[ ]
BACKSAVE
When using the TempTracker mod+ Hybrid in a BACnet MS/TP network, the use of BACnet Interface Module is required (#651735).
In addition, each of the Boiler Type and Sensor Type Startup menu option will offer a different list of BACnet variables. See "Boiler
Type" on page 20. See "Sensor Type" on page 20. Also, see "Hybrid - Outdoor Reset - BACnet Variable list" on page 44

Enable,Disable Default:Disable
Button: MENU/<System Startup>/.... Sensor Fault/BACnet Mode
This menu option enables or disables the BACnet MSTP capability. When enabled,
additional BACnet settings shall be available for further customizing.
Note that if this option was enabled while no BACnet communication is present, the BAcnet
error message will supersede other messages. See "Display Messages" on page 40.
---BACNETMODE---
Disable
Enable
BACKSAVE

9600,19200,38400 Default:19200
Button: MENU/<System Startup>/.... Sensor Fault/BACnet Mode/BACnet Baudrate
For the control to communicate over a BAcnet MS/TP network, it must use the same Baud
rate as the rest of the network. The control offers three Baud Rates.
If communication was not successful, the baud rate could be the cause. Check with the
network administrator for the network baud rate. Then match it on the control.
-BACNETBAUDRATE-
9600
19200
38400
BACKSAVE

1to127 Default:64
Button: MENU/<System Startup>/.... /BACnet Mode/BACnet Baudrate/ MSTP Address
Each device on the MS/TP network must have a unique address.
This is the MS/TP address on a RS485 network. Its MS/TP range is 1 though 127.
The MS/TP address must be provided by the Network Administrator.
----MS/TPADDRESS----
64
[ ]
BACKSAVE

1to4,000,000 Default:477,000
Button: MENU/<System Startup>/.... / MSTP Address / BACnet ID
The BACnet ID is a unique 32 bit number that identies the control within the BACnet
network. No two ID shall be the same even if dealing across networks.
It must be provided by the BACnet Network Administrator.
----BACNETID----
477000
[ ]
BACKSAVE