INSTALLATION & OPERATINGINSTRUCTIONSCATALOG NO. 6000.57G Effective: 05-27-10 Replaces: 12-12-08 P/N 241086 Rev. 8WARNING: If these instructions ar
10181-261 H4/WH1 (Low NOx)
11Wiring Diagrams—330-400 H4/WH1 (Atmospheric)
12331-401 H4/WH1 (Low NOx)
13D12.95C1.884.38SEE TABLE D FORDIMENSIONAL DATAModelNo.A B C D181 18.13 12.38 7.88 4.25182 18.13 12.38 7.88 4.25260 18.13 12.38 7.88 4.25261 18.13 12
14Sequence of OperationOn call for heat, the D-2 Power Vent fan (and appli-ance pump) start. When the flow switch circuits close,the ignition system c
15123456789101112131415Call Out Description 181-261 330-401F487800F487800yaleR1F651800F651800rewolB23NO Pressure Switch 008062F 008135F4Elbow 4"-
www.raypak.com Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468Litho in U.S.A.
2Rev. 8 reflects the following:Changes to: Fig. 2 on page 5, Fig. 4 on page 7, Fig, 5 on page 8, Dimensional Drawing on page 13, Illustrated Parts Lis
Warnings 3Pay Attention to These Terms 3Receiving Equipment 4General Specifications 4Installation 4Mounting the Assembly 4Wiring a Power Vent Assembly
Receiving EquipmentOn receiving your equipment, check the carton visual-ly for external damage. If the carton is damaged, makeanote on the Bill of Lad
57. Mount the Power Vent on the outer top.8. Route the conduit harness of the Power Vent thruthe outer top hole, around the adapter towards theback of
6U.S. Installations1Canadian Installations2AClearance above grade, veranda, porch, deck, or balcony1 ft (30 cm) 1 ft (30 cm)BClearance to window or do
7Wiring a Power Vent Assemblyto an Appliance with IIDIgnitionVentingThe vent pipe must be the same size or one size larg-er than what is indicated. Th
8LEFT SIDEThe D-2 Power Vent assembly includes a wire harness, shown in Fig. 6 below, which provides quick connec-tions with the respective controls i
9Wiring Diagrams—182-260 H4/WH1 (Atmospheric)